Networking HONYIS LiFePO4 Lithium Li-ion Battery Backup Mount UPS With Power Bank 3kva Online 120VAC UPS

1 Set
MOQ
Networking HONYIS LiFePO4 Lithium Li-ion Battery Backup Mount UPS With Power Bank 3kva Online 120VAC UPS
Features Gallery Product Description Request A Quote
Features
Specifications
Warranty: 1 Year
Model Number: Galleon R11-LI
Phase: Single Phase
Protection: Overcurrent
Type: On-line
Application: Networking
Basic Infomation
Model Number: Galleon R11-LI
Payment & Shipping Terms
Product Description
Overview

* True double-conversion

* Microprocessor control optimizes reliability

* Input power factor correction

* Wide input voltage

* ECO mode energy saving

* Emergency power off (EPO) function

* Provides over voltage cutt-off protection (OVCD)

* Provides surge immunity by MOV for full time equipment protection

* High power factor charger with very low ripple current when charging

* Low input THDi to reduce power system pollution

* Adjustable charging current via LCD panel

* Smart battery charger design to optimize battery performance

* Generator compatible

* Comprehensive display allows easy monitoring and access of UPS status

* Hot-Swappable battery design

Specifications
MODEL R11-LI-1K R11-LI-1.5K R11-LI-2K R11-LI-3K
PHASE Single phase with ground
CAPACITY 1000 VA / 900 W 1500 VA / 1350 W 2000 VA / 1800 W 3000 VA / 2700 W
INPUT
Nominal Voltage 200/208/220/230/240 VAC (100/110/115/120 /127 VAC)
Voltage Range Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 3 % (80Vac/70Vac/60Vac/55Vac ± 3%)
based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0
Low Line Comeback 175 VAC / 155 VAC / 135 VAC / 125 VAC ± 3 % (87Vac/77Vac/67Vac/62Vac ± 3%)
based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0

High Line

Transfer

300 VAC ± 3%(150Vac± 3%)
High Line Comeback 290 VAC ± 3%(145Vac± 3%)
Frequency Range 40Hz ~ 70Hz
Power Factor ≥ 0.99 @ nominal voltage (100% load)
THDi ≤ 5% @ nominal input voltage
OUTPUT
Output Voltage 200*/208*/220/230/240 VAC (100*/110/115/120 /127 VAC)

AC Voltage Regulation

(Battery Mode)

± 1%

Frequency Range

(Synchronized Range)

57~63Hz or 47 ~ 53 Hz

Frequency Range

(Battery Mode)

60 Hz ± 0.1 Hz or 50Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion 2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
Transfer Time AC to Battery Mode Zero
Inverter to Bypass <4 ms (Typical)

ECO to

Battery Mode

8 ms (Typical)
Waveform (Battery Mode) Pure Sine Wave
EFFICIENCY
AC Mode 89% @ full charged battery 90% @ full charged battery
ECO Mode 96% @ full charged battery
Battery Mode 87% 89% 90%
BATTERY
Battery Type LiFe 247500 LiFe 485000 LiFe 485000 LiFe 722500
Battery Lifecycle > 2000
Battery Numbers of Parallel 1 1 2 3
Battery Cell Configuration 8S3P 15S2P (15S2P) x 2 (24S1P) x 3
Battery Voltage 25.6V 48V 48V 76.8V
Battery VAH (Factory Setting) 7.5Ah 5Ah 10Ah 7.5Ah
Autonomy Time @ Full Load 9.5 minutes 8 minutes 12 minutes 9.5 minutes
Charging Voltage 28VDC ± 1% 52.5VDC ± 1% 52.5VDC ± 1% 84VDC ± 1%
Charging Mode 2 stage charging management(CC-CV)
Charging Current 1/2/4/6/8A(max.), adjustable through LCD
Typical Recharge Time 1.5 hours recover to 90% capacity
Easy replace battery Yes
PHYSICAL
Dimension,D x W x H (mm) 410 x 438 x 88 410 x 438 x 88 510 x 438 x 88 630 x 438 x 88
Net Weight (kgs) 10.8 11.6 15.2 20.5
ENVIRONMENT
Operating Humidity 20-95 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 50dBA Less than 55dBA
MANAGEMENT
Smart RS-232,USB Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
SNMP Power management from SNMP manager and web browser
STANDARD
EMC/Safety CE (EMC: EN62040-2 C2) for HV models; cTUVus (comply to UL1778), Fcc(Class A) for LV models
Downloads

Please get datasheet and user manual from sales if you need.

Datasheet Galleon R11-LI_1~3K_Datasheet
User Manual Galleon R11-LI_1~3K_User Manual